Positive-pole-fused 1500 V DC combining for 8, 10 or 12 PV inputs, up to 45 A per input with 65 A fuses. Output circuit breakers are rated 400 / 500 / 630 A by input count. IP65 enclosure; monitoring, communication and active protection are optional.
Positive-pole-fused 1500 V DC combining for 8, 10 or 12 PV inputs, up to 45 A per input with 65 A fuses. Output circuit breakers are rated 400 / 500 / 630 A by input count. IP65 enclosure; monitoring, communication and active protection are optional.
Where it fits
PV arrays with high-current strings, using 8, 10 or 12 inputs and positive-pole fusing. Confirm the complete design and operating conditions when determining allowable continuous cabinet output.
Key features
45 A per input, 65 A fuses Positive-pole-fused configurations with 8, 10 or 12 inputs, rated up to 45 A per input and fitted with 65 A fuses.
Three input configurations Output circuit breaker ratings are 400 A for 8 inputs, 500 A for 10 inputs and 630 A for 12 inputs. These are component ratings; continuous cabinet output depends on the complete design and operating conditions.
Optional monitoring and active protection String current, bus voltage and switch/SPD status monitoring, communication, active protection, active/broadcast tripping, energy/power monitoring, reverse-current protection and active fire suppression are optional. Current and voltage monitoring modules and tripping controls are developed by CFGE.
IP65 outdoor enclosure Wall mounting or horizontal installation, with operation from -25 to +60 °C and no derating up to 2,000 m. Dimensions are 800 × 850 × 200 mm (W × H × D), with a cabinet weight of 48.7 kg.
Specifications+
Series Configuration
8 inputs
10 inputs
12 inputs
Maximum input voltage
1,500 V DC
1,500 V DC
1,500 V DC
Number of inputs
8
10
12
Maximum current per input
45 A
45 A
45 A
Fuse rated current
65 A
65 A
65 A
Output circuit breaker rating
400 A
500 A
630 A
Environment and Installation
Operating temperature
-25 to +60 °C
Storage temperature
-30 to +70 °C
Relative humidity
99%, non-condensing
Operating altitude
≤ 2,000 m, no derating
Ingress protection
IP65
Mounting
Wall mounting / horizontal installation
Protection and Monitoring
Fuse protection polarity
Positive-pole fusing
Fuse rated voltage / current
1,500 V DC / 65 A
Output circuit breaker
1,500 V DC; 400 / 500 / 630 A, configured according to input count
Switch operation
Internal / external handle with door interlock and LOTO
SPD type
Type I+II standard; Type I / Type II optional
SPD rated voltage
1,500 V DC
String current / bus voltage
Monitoring optional
Switch / SPD status
Monitoring optional
Communication / protocol
Communication optional
Current sensing
Shunt resistor / Hall sensor
Monitoring power supply
Self-powered
Smart Function Configuration
Bus short-circuit / active protection
Optional
Active / broadcast tripping
Optional
Energy / power monitoring
Optional
Reverse-current protection
Optional
Active fire suppression
Optional
Dimensions and Weight
Dimensions (W × H × D)
800 × 850 × 200 mm
Cabinet weight
48.7 kg
Standards and Certifications
Standards listed in the data sheet
IEC 61439-1/2, IEC 62109-1, EN 61000-6, UL 1741, AS 3000, AS 5033, GB/T 34936
Specifications from the CFGE 1500 V High-Current DC Combiner Box data sheet, High-Current Series Positive Fused. Output breaker ratings are component ratings. The input limit is 45 A per circuit; allowable continuous cabinet output depends on the complete design and operating conditions. Monitoring, communication and smart functions are optional as specified in the tables.
Datasheet+