Outdoor liquid-cooled 418 kWh cabinets for C&I storage, in two versions: a DC-side battery cabinet at 1331.2 V and 209 kW for an external PCS, and an all-in-one cabinet with bidirectional PCS, EMS and BMS delivering 125 kW at 400 V or 215 kW at 690 V, on-grid and off-grid.
Outdoor liquid-cooled 418 kWh cabinets for C&I storage, in two versions: a DC-side battery cabinet at 1331.2 V and 209 kW for an external PCS, and an all-in-one cabinet with bidirectional PCS, EMS and BMS delivering 125 kW at 400 V or 215 kW at 690 V, on-grid and off-grid.
2 versions
Version
DC side
All-in-One
Model
DC/418-PT/GL
CFGE 215K/418-PT/GL
Type
DC-side battery cabinet for an external PCS
All-in-one cabinet with bidirectional PCS, EMS and BMS
C&I storage with eight battery packs, BMS and liquid thermal management in one outdoor cabinet. Choose the DC-side cabinet when the project already has a PCS and EMS: its quick-connect DC interface and CAN / RS485 / Ethernet communication connect to them, with a 220 V AC auxiliary supply. Choose the all-in-one cabinet to connect directly to a 400 V or 690 V grid, on-grid or off-grid.
Key features
Two versions, one 418 kWh platformA DC-side cabinet for an external PCS, or an all-in-one cabinet with a bidirectional PCS, EMS and BMS. Both hold eight packs of 314 Ah LFP cells at 1,331.2 V DC.
On-grid and off-gridThe all-in-one version delivers 125 kW at 400 V or 215 kW at 690 V, with active and reactive power control and off-grid operation.
Liquid cooling and heatingAutomatic liquid cooling and low-temperature preheating in an IP55 outdoor cabinet.
Hierarchical battery managementBMU and cluster-level management monitor voltage, temperature and SOC, with insulation detection and relay adhesion detection.
Cabinet-level fire protectionAerosol extinguishing with smoke and heat detection and an audiovisual alarm; the all-in-one adds a cabinet firefighting water inlet and a vent valve.
Specifications+
Battery and DC
DC side
All-in-One
Rated energy
418 kWh
Cell chemistry / capacity
LFP / 3.2 V / 314 Ah
Battery configuration
1P416S (8 × 1P52S packs)
Nominal DC voltage
1,331.2 V DC
DC voltage range
1,040 – 1,497.6 V DC
1,164.8 – 1,497.6 V DC
DC current
157 A continuous charge / discharge
185 A maximum
Rated cabinet charge / discharge power
209 kW
—
Standard charge / discharge rate
—
0.5P
DC Protection and Interfaces
DC side
Disconnect switch rating
1,500 V DC / 250 A
Main positive fuse rating
1,500 V DC / 350 A
DC connection
Quick-connect
External communication
Communication with PCS / EMS
On-Grid AC · All-in-One
400 V configuration
690 V configuration
Rated AC power
125 kW
215 kW
Rated AC current
180 A
AC wiring
Three-phase four-wire (3L + N)
Three-phase three-wire (3L)
Grid voltage range
400 V ±10%
690 V ±10%
Grid frequency
50 / 60 Hz ±2.5 Hz
Current THD
< 3% at rated power
Long-term overload
110% (ambient ≤ 40 °C)
Off-Grid AC
All-in-One
Off-grid output voltage
400 / 690 V AC ±10% (by configuration)
Off-grid output frequency
50 / 60 Hz
Off-grid voltage THD
≤ 3% (linear load)
System and Environment
DC side
All-in-One
Dimensions (W × D × H)
1,313.2 × 1,300 × 2,402 mm
1,350 × 1,350 × 2,500 mm
Cabinet weight
Approx. 3,650 kg
Approx. 3,900 kg
Cabinet ingress protection
IP55
Corrosion protection
C4
—
Installation
Outdoor
System efficiency
—
≥ 88%
Cooling / heating
Liquid cooling; liquid heating
Cooling capacity / heating power
—
8 kW (W18/L45) / 2 kW
Ambient operating temperature
−30 to +50 °C
−25 to +55 °C; derating above 45 °C
Charge / discharge operating temperature
Charge +5 to +50 °C; discharge −15 to +50 °C
—
Relative humidity
—
≤ 95%, non-condensing
Storage humidity / SOC
RH ≤ 90%; SOC 30 – 50%
—
Operating altitude
≤ 2,500 m
≤ 2,000 m; derating above 2,000 m
Communication interfaces
CAN / RS485 / Ethernet
Cable entry
—
Bottom entry
Auxiliary Power Supply
DC side
Auxiliary supply voltage
220 V AC ±15%
Auxiliary supply frequency
50 / 60 Hz ±3 Hz
Maximum auxiliary supply current
30.2 A
Management and Safety
DC side
All-in-One
Energy / battery management
Hierarchical BMU and cluster management (BMU + BCU / BCMU)
EMS in the main cabinet + BMS (BCMU / BMU)
Monitoring and balancing
Voltage, temperature, SOC; passive balancing
—
Detection and protection
Insulation and relay adhesion detection; fault alarms
—
Power control
—
Bidirectional charge / discharge; active and reactive power control
VDE 4105, AS 4777.2, G99 Type A, EN 50549-1/2/10, IEC 61727, IEC 62116, NA/EEA-NE7-CH:2020, NC RfG, PSE, PTPiREE
Specifications from the CFGE 418 Series data sheets, global version. Switch and fuse ratings are component ratings; cabinet operating current and power are limited by the battery, BMS and system configuration. All-in-one rated AC power depends on the voltage configuration; actual power is subject to battery status, BMS limits and operating conditions. Low-temperature operation requires suitable battery temperature and BMS permission: ambient limits do not define the direct battery charge / discharge temperature limits.
Datasheet+
Datasheets for each version downloads directly as PDF in English and Chinese. No registration needed.