An IP55 outdoor STS transfer and distribution cabinet for two or more storage cabinets. ESTS500-M transfers from on-grid to off-grid in under 20 ms, with a 500 kW grid-side budget, up to 250 kW total battery charging and up to 250 kW load-side power.
An IP55 outdoor STS transfer and distribution cabinet for two or more storage cabinets. ESTS500-M transfers from on-grid to off-grid in under 20 ms, with a 500 kW grid-side budget, up to 250 kW total battery charging and up to 250 kW load-side power.
Where it fits
The grid-side power budget is 500 kW, with maximum total battery charging power of 250 kW and maximum load-side power of 250 kW. When more than two storage cabinets are connected, charging is allocated within the aggregate 250 kW storage-side limit. Reducing charging power per cabinet allows more cabinets to be connected.
Key features
Fast grid transfer The integrated ESTS500-M transfers from on-grid to off-grid in under 20 ms.
Two or more storage cabinets Connections are sized to actual charging demand within the 250 kW aggregate storage-side charging limit.
Integrated protection and UPS STS, UPS, shunt-trip circuit protection, surge protection, emergency stop and status indication in one cabinet.
IP55 outdoor installation Bottom cable entry and exit for outdoor storage-system integration.
Specifications+
AC Connection
Cabinet rated voltage
400 V AC
Storage cabinets connected
Two or more; subject to actual charging power requirements
STS grid-side maximum power
500 kW
STS grid-side rated current
722 A
Maximum total storage charging power
250 kW
Maximum load-side power
250 kW
Automatic Transfer with STS
STS model
ESTS500-M
On-grid to off-grid transfer
< 20 ms
STS voltage / tolerance
380 / 400 V AC, ±15%
STS rated frequency
50 / 60 Hz, ±5 Hz
STS communication
RS485 / CAN / Ethernet
Protection and Auxiliary Equipment
Grid main breaker QF1
400 V AC / 1,000 A, shunt trip
Storage breaker QF2 (No. 1)
400 V AC / 250 A
Storage breaker QF3 (No. 2)
400 V AC / 250 A
Load breaker QF4
400 V AC / 500 A
Surge protective device
Type II; 20 kA / 40 kA; 4P
Auxiliary / backup supply
AC 220 V / DC 24 V, 240 W; 24 V backup battery
Emergency stop / indication
Emergency stop; power, run and fault indicators
Enclosure and Installation
Dimensions (W × D × H)
1,200 × 1,350 × 2,150 mm
Cabinet weight
1,100 ± 10 kg
Cabinet ingress protection
IP55
Location / operating altitude
Outdoor, ≤ 2,000 m
Cable entry / exit
Bottom entry and exit